Your balance point
—
| Outdoor temp | COP | Heat pump / kWh | Backup / kWh | Cheaper |
|---|
At the US defaults, the break-even COP against gas is 3.38 — the heat pump must stay above a COP of 3.38 to heat more cheaply than gas, which it does down to the balance point of 5.8 °C. Above 5.8 °C the heat pump is cheaper; below it, gas is cheaper.
For the full explanation, see our Heat Pump Balance Point Guide. To compare annual running costs, use the Heat Pump Savings Calculator, and to check what capacity your home needs, use the Heat Pump Size Calculator.
How it works
A heat pump's efficiency — its COP (coefficient of performance) — falls as the outdoor temperature drops. This calculator assumes COP falls linearly between your two rated points: at any temperature in between, the COP is interpolated in a straight line from the mild rating to the cold rating.
Backup cost per kWh of heat = (fuel price ÷ kWh per unit of fuel) ÷ (efficiency ÷ 100)
Heat pump cost per kWh of heat = electricity rate ÷ COP at that temperature
COP needed to break even = electricity rate ÷ backup cost per kWh of heat
The balance point is where electricity ÷ COP equals the backup's cost per kWh of heat — the temperature at which the interpolated COP falls to exactly the break-even COP. Above that temperature the heat pump is cheaper; below it, the backup is cheaper.
What this calculator does not include
- Linear COP interpolation is an approximation. A real COP curve is not perfectly straight between the two rated points, and manufacturers' test conditions vary.
- No defrost-cycle penalty. In cold, damp weather a heat pump periodically reverses to defrost its outdoor coil, which temporarily lowers its effective COP. That cost is not modelled here.
- No backup-heater capacity limits. This calculator does not check whether your heat pump can physically meet your home's heat loss at low temperatures.
- This is the ECONOMIC balance point, not the thermal (capacity) balance point. It answers "which is cheaper?", not "which can keep the house warm on its own?". Below the thermal balance point you need backup heat for capacity, whatever the prices say.
- Standing charges, maintenance, carbon pricing changes and future fuel-price movements are not included.
Frequently asked questions
What is the economic balance point of a heat pump?
The economic balance point is the outdoor temperature below which your backup fuel makes heat more cheaply than the heat pump. Above it the heat pump wins on running cost; below it the backup wins, because the heat pump's COP falls as it gets colder while the backup's cost per kWh of heat stays the same.
How is the balance point calculated?
First work out the backup's cost per kWh of heat: fuel price divided by the kWh in each unit of fuel, divided by the system's efficiency. Then divide your electricity price by that cost to get the COP the heat pump must beat. The balance point is the temperature where the heat pump's COP, interpolated between its two rated points, falls to exactly that break-even COP.
What is the difference between the economic and thermal balance point?
The economic balance point is about cost: where the cheaper heat source changes. The thermal (or capacity) balance point is about output: the temperature below which the heat pump can no longer meet the home's heat loss on its own and needs backup heat for capacity, regardless of price. This calculator finds the economic balance point only.
What should I set my auxiliary heat lockout to?
If your system lets you set an auxiliary-heat lockout or compressor lockout temperature, setting it near your economic balance point is a sensible starting point, so the switchover happens automatically when the backup becomes cheaper. Check your manufacturer's guidance first, and remember that on the very coldest nights you may still need backup heat for capacity even if the heat pump is cheaper per kWh.
What switchover temperature should I set for a dual-fuel system?
Set it at or near the economic balance point, not the thermal one. At the US defaults in this calculator, the economic balance point against gas is 5.8 °C: above that temperature the heat pump heats for less, and below it the furnace heats for less. Setting the switchover near your own calculated balance point therefore switches to the cheaper source automatically as the weather changes.
What if my heat pump has no balance point?
It means the heat pump beats the backup fuel at every temperature in the range you entered, so there is no temperature where the backup becomes cheaper. This happens, for example, in the UK against gas and in the US against oil or propane at the default rates. The calculator handles this case: it reports no balance point and shows the heat pump as cheaper throughout, so you can run it all winter and keep the backup for capacity on the very coldest nights.
Related calculators
- Heat Pump Savings Calculator — annual running-cost savings vs gas, oil, propane or electric heating.
- Heat Pump Size Calculator — what capacity your home needs.
- Heating Cost Comparison Calculator — side-by-side annual cost of every heating fuel.
- Guide: What is a heat pump balance point? — the full explanation, with worked examples.
- Methodology — how every WattWorth Calc calculator works and where its rates come from.
Sources: US electricity and fuel rates — U.S. Energy Information Administration (EIA); UK rates — Ofgem price cap; Canada rates — Canada Energy Regulator; COP ranges — U.S. Department of Energy. Rates last verified November 2026.